Current Calculation of 3 Phase Induction Motor

    Formulas:

    Single Phase AC Motor FLA (Amperes) = (P [kW] × 1000) / (V × cos ϕ)

    Single Phase AC Motor FLA (Amperes) = (P [HP] × 746) / (V × cos ϕ × η)

    Three Phase AC Motor FLA (Amperes) = (P [kW] × 1000) / (V × 1.732 × cos ϕ)

    Three Phase AC Motor FLA (Amperes) = (P [HP] × 746) / (V × 1.732 × cos ϕ × η)

    Where:

    • P [HP], P [kW] = Motor power rating (HP or kW)
    • V = Motor rated voltage (Volts)
    • η = Motor efficiency in decimal form
    • cos ϕ = Motor power factor
    • 1000 = Conversion factor to convert kW to W
    • 746 = Conversion factor to convert HP to W

    Motor Configuration

    Enter all values to see the result

    Tags:

    Induction Motor Current Calculation, 3 phase motor, ampere, FLC CALCULATOR FOR MOTOR, hp, KW, Motor full load current calculator, single phase motor